王中王四不像玄机图

念海消防

产品中心

support hotline

0512-67951790
  • 悬挂式七氟丙烷(电磁型)
Heptafluoropropane (electromagnetic type)

七氟丙烷灭火装置(电磁驱动型)是以七氟丙烷作为灭火剂,将灭火剂储存罐体、电磁式瓶头阀、电磁阀、压力显示部件等组件预先装配成独立的、可悬挂安装(或固定于墙壁上)的、利用一些火灾探测元件和气体灭火控制器等组成的集火灾探测、报警和灭火功能于一体的一类灭火装置。 Suspension heptafluoropropane fire extinguishing device (electromagnetic drive type) uses heptafluoropropane as a fire extinguishing agent. The fire extinguishing agent storage tank, electromagnetic bottle head valve, solenoid valve, pressure indicator and other components are pre-assembled into independent, hanging installation (or fixed On the wall), a type of fire extinguishing device that integrates fire detection, alarm and fire extinguishing functions with some fire detection elements and gas fire extinguishing controllers.

National Hotline

0512-67951790

技术参数

七氟丙烷灭火器装置(电磁驱动型)主要技术参数 Main technical parameters of hanging heptafluoropropane fire extinguisher device (electromagnetic drive type)

Model specifications

kg Maximum charge of fire extinguishing agent ( kg )

mm) Dimensions × height ( mm)

20 °) Storage pressure ( 20 °)

Start way

1 . 6 XQQC10 / 1. 6

1 . 5 1 1. 5

× 500 350 × 500

.6Mpa 1 .6Mpa

Electromagnetic drive

DC24V/1A ( DC24V / 1A )

XQQC20 / 1.6

twenty three

× 540 400 × 540

XQQC30 / 1.6

34.5

× 560 450 × 560

XQQC40 / 1.6

46

× 570 500 × 570

系统简介


System composition :

Electrically controlled hanging heptafluoropropane fire extinguishing device, gas fire extinguishing controller, fire detector, sound and light alarm, gas release indicator, emergency start and stop button, external power supply, etc. form a complete automatic gas fire extinguishing system

Product features :
1. The gas fire controller is used to collect the signals detected by the detection elements to start the solenoid valve, which is stable, reliable and sensitive.
2. Environmental protection and safety, no harm to human body and precision equipment and other precious property.
3. Accurate and reliable work, short spray time and rapid fire extinguishing
4. Simple construction and installation, low engineering investment, and does not occupy the area of the protective area;
5. According to the special conditions of the place of use, a variety of choices can be made for the detection element.

Use range :

BC各类火灾,能安全有效地使用在无人或有人的场所 1. It is used to put out various fires of A , B , and C. It can be used safely and effectively in unmanned or manned places.

2.Suitable for places where no traces are left after the fire extinguishing agent is sprayed or it is difficult to clean the residue

3.Suitable for places containing valuables, priceless treasures, precious files, software and hardware

4. Particularly suitable for: fire protection of small protective areas such as communication base stations, computer rooms, power distribution rooms, etc.

类活泼金属及含有氧化剂、能自行分解的化合物和可燃固体物质的深位火灾 5.Not suitable for deep fires of Class D active metals and compounds containing oxidants, self-decomposable compounds and combustible solid substances

System maintenance plan :

Check

(1) Daily inspection of the appearance and pressure indication of the device by trained personnel every day.

(2) Check the pressure gauge at least once every quarter. After the pointer exceeds the green zone or after use, the manufacturer or the fire engineering unit that has been trained and qualified for professional installation shall be entrusted to perform maintenance.

(3) Weigh and inspect the fire extinguisher storage bottle once a year. If the weight of the storage bottle drops more than 5% of the total weight, the bottle must be refilled or replaced; perform an action test on the solenoid valve of the electromagnetic fire extinguishing device every year. Can only be used after passing the test.

(4) The storage bottle should be regularly inspected in accordance with relevant national standards such as the “Cylinder Safety Supervision Regulations” and can only be used after being qualified. If there is rust, the storage bottle should be treated for rust prevention. While checking the storage bottle, perform a hydraulic strength test on all valves as required.

2. Maintenance

(1) The gas fire extinguishing device must always be in good working condition, and the maintenance personnel must be specially trained. Any failure or damage to the fire extinguishing device must be repaired in time and detailed records should be made.

(2) After the gas fire extinguishing device is used (discharged), it shall be entrusted to the manufacturer or a fire station who has been trained to obtain a professional installation qualification for maintenance.

3. Staff training

(1) The user shall conduct strict and comprehensive training for all personnel who may be responsible for inspecting, using and maintaining the system.

(2) The company is responsible for providing technical services in terms of maintenance, inspection and personnel training. If necessary, you can contact us by mail.

5大服务优势

总1






Hot product
管网七氟丙烷灭火系统

Pipe network heptafluoropropane fire extinguishing system

Features: 1. Combined allocation, can protect 2-8 protected areas at the same time. 2. The gas cylinders are fixedly installed in specific gas cylinders and do not take up space in the protective area. 3. Pipe network heptafluoropropane fire extinguishing system nozzles are evenly distributed, more evenly discharged, which is conducive to fire extinguishing. Application Scenario: Pipe network sevoflurane fire extinguishing system can be used to protect places with frequent people and high-precision electronic instruments, communication equipment and other high-value property and important places. It is suitable for fighting A, B, C and E electrical fires, such as Communication room, high and low voltage distribution room, archive room, energy storage container, industrial cleaning equipment, dangerous goods warehouse and other flammable and explosive places.
柜式超细干粉灭火装置

Cabinet type superfine dry powder fire extinguishing device

[Characteristics of cabinet-type ultra-fine dry powder fire extinguishing device]: Beautiful appearance, simple structure, convenient and quick start. The cabinet type ultra-fine dry powder fire extinguishing device is linked with the fire detection and alarm system, which is suitable for both full submerged automatic fire extinguishing and large area local protection.
气体灭火报警主机

Gas fire alarm host

System introduction: The gas fire extinguishing controller is mainly used for various fire extinguishing systems such as piped or non-piped heptafluoropropane, high pressure carbon dioxide, ig541, aerosol and fire extinguishing systems such as ultra-fine dry powder, which can be directly connected to smart smoke and temperature fires. The detector can also be connected to a non-coded fire detector through a smart non-coded detector interface (relay module) to perform a fire alarm.
IG-541混合气体灭火系统

IG-541 mixed gas fire extinguishing system

[Features]: lG-541 mixed gas fire extinguishing agent is a colorless, odorless, non-toxic, non-conductive, pure "green" clean fire extinguishing agent. It does not produce temperature differences and unfavorable decomposition products during the fire extinguishing process. Remnants. [Scope of application]: lG-541 mixed gas fire extinguishing system can be used to remedy various types of fires that can extinguish A, B, and C. Because of its strong safety, it does not damage the object of protection, and does not affect people's vision during fire extinguishing, so Can be used in places where people often work.

Nianhai Fire Fighting

Focus on providing fire protection solutions in key protective areas 0512-67951790